Work out your data centre’s PUE

Total facility energy divided by IT energy, over the same twelve months.

Enter your readingsWhat PUE is

Two readings

Where is IT energy read?
Cost, carbon, target

CEA, FY 2025-26.

Example: Case A, all electric

PUE 1.70

17,05,000 ÷ 10,00,000 = 1.705

IT equipment 58.7%Everything else 41.3%
Everything else
7,05,000 kWh
Carbon, all of it
1,151 t CO2
Carbon, everything else
476 t CO2

Type your two readings.

The calculator needs JavaScript; the example was worked at build time.

What you type is not saved or sent.

Where the meter sits

CategoryIT energy read atWhat is readWritten as
0The UPS outputPeak kWPUE₀
1The UPS outputkWh, 12 monthsPUE₁
2The PDU outputkWh, 12 monthsPUE₂
3Each IT device’s plugkWh, 12 monthsPUE₃
A published PUE names its category; the total is read where energy enters. source

A year at Case A

The task force’s all-electric example. source

PUE 1.70

Went onkWhShareWhere the energy goes
IT load10,00,00058.7%
Cooling4,00,00023.5%
Power delivery loss2,50,00014.7%
Lighting50,0002.9%
Other5,0000.3%
Total17,05,000100.0%

What PUE leaves out

  • Where power comes from

    Buying solar or wind power leaves a PUE unchanged. source

  • What the servers do

    PUE stops at the IT equipment; server efficiency is another measure. source

  • Another site

    Rule out reliability and climate before comparing two sites. source

  • Fuel and chilled water

    Each is weighted first; this calculator takes electricity only. source

The grid, in carbon

0.774 in FY 2013-14

0.675

t CO2 per MWh, FY 2025-26

CEA’s average for India’s grid. The calculator multiplies each kWh by it. source

The rule, in its own words

What PUE is

PUE is defined by the following formula: PUE = (Total data center energy consumption or power / IT energy consumption or power)

Section 3, the task force paper