Work out your data centre’s PUE
Total facility energy divided by IT energy, over the same twelve months.
Two readings
Example: Case A, all electric
PUE 1.70
17,05,000 ÷ 10,00,000 = 1.705
- Everything else
- 7,05,000 kWh
- Carbon, all of it
- 1,151 t CO2
- Carbon, everything else
- 476 t CO2
Type your two readings.
The calculator needs JavaScript; the example was worked at build time.
What you type is not saved or sent.
Where the meter sits
| Category | IT energy read at | What is read | Written as |
|---|---|---|---|
| 0 | The UPS output | Peak kW | PUE₀ |
| 1 | The UPS output | kWh, 12 months | PUE₁ |
| 2 | The PDU output | kWh, 12 months | PUE₂ |
| 3 | Each IT device’s plug | kWh, 12 months | PUE₃ |
| Went on | kWh | Share | Where the energy goes |
|---|---|---|---|
| IT load | 10,00,000 | 58.7% | |
| Cooling | 4,00,000 | 23.5% | |
| Power delivery loss | 2,50,000 | 14.7% | |
| Lighting | 50,000 | 2.9% | |
| Other | 5,000 | 0.3% | |
| Total | 17,05,000 | 100.0% |
What PUE leaves out
Where power comes from
Buying solar or wind power leaves a PUE unchanged. source
What the servers do
PUE stops at the IT equipment; server efficiency is another measure. source
Another site
Rule out reliability and climate before comparing two sites. source
Fuel and chilled water
Each is weighted first; this calculator takes electricity only. source
The grid, in carbon
0.774 in FY 2013-14
0.675
t CO2 per MWh, FY 2025-26
CEA’s average for India’s grid. The calculator multiplies each kWh by it. source
The rule, in its own words
PUE is defined by the following formula: PUE = (Total data center energy consumption or power / IT energy consumption or power)